Our KACO2 records the ambient air's CO2 concentration in air ducts of air-conditioning systems. The KACO2 converts the the values measured in the ranges of optionally 0-2000 ppm or 0-5000 ppm into a linear 0-10 V output signal. The CO2 value is measured via the NDIR sensor, which is able to compensate possible pollution with the help of its 2-ray measuring principle. Optionally, our KACO2 is available with an additional sensor for measuring temperature and humidity.
Features
Power supply: At 0 … 10 V: 16 … 24 VDC or 24 VAC
At 4 … 20 mA: 16 … 24 VDC
Power consumption: < 9 mA
Electrical connection: Screw clamps
Output: 0 … 10 V lub 4-20 mA
Sensor element: (NDIR) sensor with automatic backgroand calibration 0 …
Measuring range CO2: 0 … 2000 ppm
Accuracy: < ± (50ppm 2% of scale reading) at 25°C and 1013 mbar
Temperature: 0 … 10 V lub 4-20 mA / -30 °C … +70 °C
Accuracy: ± 0,5 °C
Humidity: 0 … 10 V lub 4-20 mA / 0 … 100% r.h.
Accuracy: < ± 3% at 25°C between 10..90% r.h.
Operating temperature: -20 °C … +50 °C
Humidity: 10 … 95% r.h.
Protection class: IP65 (housing)
Casing: Plastic
Mounting equipment (included): Mounting fange